ABB AC500 PLC - Group Parameters for the Analog Part

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 154: Settings "Error LED / Failsafe function"
Setting Description
On Error LED (S-ERR) lights up at errors of all error classes, Fail-
safe mode off
Off by E4 Error LED (S-ERR) lights up at errors of error classes E1, E2
and E3, Failsafe mode off
Off by E3 Error LED (S-ERR) lights up at errors of error classes E1 and
E2, Failsafe mode off
On +Failsafe Error LED (S-ERR) lights up at errors of all error classes, Fail-
safe mode on *)
Off by E4 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1, E2
and E3, Failsafe mode on *)
Off by E3 + Failsafe Error LED (S-ERR) lights up at errors of error classes E1 and
E2, Failsafe mode on *)
*) The parameters Behaviour analog outputs at communication error and Behaviour digital out-
puts at communication error are only evaluated if failsafe function is enabled.
Group Parameters for the Analog Part
Name Value Internal value Internal value,
type
Default
Analog data
format
Standard
Reserved
0
255
BYTE 0
Behaviour analog
outputs at com-
munication error
*)
Off
Last value
Last value 5 s
Last value 10 s
Substitute value
Substitute value
5 s
Substitute value
10 s
0
1
6
11
2
7
12
BYTE 0
*) The parameter Behaviour analog outputs at communication error is only analyzed if the Fail-
safe mode is ON.
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/17 3ADR010121, 13, en_US 961