ABB AC500 PLC - Input;Output Characteristics of CI501-PNIO

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Supported protocols RTC - real time cyclic protocol, class 1 *)
RTA - real time acyclic protocol
DCP - discovery and configuration protocol
CL-RPC - connectionless remote procedure
Call
LLDP - link layer discovery protocol
MRP - MRP Client
Acyclic services PNIO read / write sequence (max. 1024 bytes
per telegram)
Process-Alarm service
Supported alarm types Process Alarm, Diagnostic Alarm, Return of
SubModule, Plug Alarm, Pull Alarm
Min. bus cycle 1 ms
Conformance class CC A
Protective functions (according to IEC
61131-3)
Protected against:
short circuit
reverse supply
overvoltage
reverse polarity
Electrical isolation from the rest of the module
*) Priorization with the aid of VLAN-ID including priority level
Input/Output Characteristics of CI501-PNIO
The PROFINET Bus Module CI501-PNIO is used as decentralized I/O module in PROFINET
networks. The network connection is performed via 2 RJ45 connectors which are integrated in
the Terminal Unit. The Bus Module contains 22 I/O channels with the following properties:
4 analog inputs (1.0...1.3), configurable as:
-10 ... +10 V
0 ... +10 V
-10 ... +10 V (differential voltage)
0 ... 20 mA
4 ... 20 mA
Pt100 , Pt1000, Ni1000 (for each 2-wire and 3-wire)
24 V digital input function
2 analog outputs (1.5...1.6), configurable as:
-10 ... +10 V
0 ... 20 mA
4 ... 20 mA
8 digital inputs 24 V DC in 1 group (2.0...2.7)
8 digital transistor outputs 24 V DC (0.5 A max.) in 1 group (3.0...3.7)
Resolution of the analog channels: 12 bits
The inputs/outputs are electrically isolated from the Ethernet network. There is no potential sep-
aration between the channels. The configuration of the analog inputs/outputs is performed by
software.
For usage in enhanced ambient conditions (e.g. wider temperature and humidity range), a spe-
cial XC version of the device is available.
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/17 3ADR010121, 13, en_US 1005