Internal value Operating modes of the analog inputs, individually configurable
19 3-wire Ni1000 -50 °C...+150 °C *)
*) In the operating modes with 3-wire configuration or with differential
inputs, two adjacent analog inputs belong together (e.g. the chan-
nels 0 and 1). In these cases, both channels are configured in the
desired operating mode. The lower address must be the even
address (channel 0). The next higher address must be the odd
address (channel 1). The converted analog value is available at the
higher address (channel 1).
Table 84: Channel Monitoring
Internal Value Check Channel
0 (default) Plausib(ility), cut wire, short circuit
3 Not used
Channel Parameters for the Analog Outputs (2x)
Name Value Internal value Internal
value, type
Default EDS Slot /
Index
0
Output 0,
Channel con-
figuration
see
Ä
Table 85 “C
hannel Con-
figuration”
on page 589
see
Ä
Table 85 “C
hannel Con-
figuration”
on page 589
BYTE 0 0x0Y11
Output 0,
Check
channel
see
Ä
Table 86 “C
hannel moni-
toring”
on page 589
see
Ä
Table 86 “C
hannel moni-
toring”
on page 589
BYTE 0 0x0Y12
Output 0,
Substitute
value
see
Ä
Table 87 “S
ubstitute
Value”
on page 589
see
Ä
Table 87 “S
ubstitute
Value”
on page 589
WORD 0 0x0Y13
Output 1,
Channel con-
figuration
see
Ä
Table 85 “C
hannel Con-
figuration”
on page 589
see
Ä
Table 85 “C
hannel Con-
figuration”
on page 589
BYTE 0 0x0Y14
Output 1,
Check
channel
see
Ä
Table 86 “C
hannel moni-
toring”
on page 589
see
Ä
Table 86 “C
hannel moni-
toring”
on page 589
BYTE 0 0x0Y15
Output 1,
Substitute
value
see
Ä
Table 87 “S
ubstitute
Value”
on page 589
see
Ä
Table 87 “S
ubstitute
Value”
on page 589
WORD 0 0x0Y16
I/O Modules > Digital/Analog I/O Modules