EasyManua.ls Logo

ABB AC500 PLC - Technical Data of the Configurable Digital Inputs;Outputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 VDC power supply at the L+/UP
and M/ZP terminals of the CPU/bus
module
Ca. 2 mA
From UP at normal operation / with out-
puts
0.15 A + max. 0.5 A per output
Inrush current from UP (at power up) 0.005 A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Sensor power supply
Connections Terminals 1.0...1.3 = +24 V, 1.4...1.7 = 0 V
Terminals 3.0...3.3 = +24 V, 3.4...3.7 = 0 V
Voltage 24 VDC with short-circuit and overload protec-
tion
Loadability Terminals 1.0...1.3, in total max. 0.5 A
Terminals 3.0...3.3, in total max. 0.5 A
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical Data of the Configurable Digital Inputs/Outputs
Each of the configurable I/O channels is defined as input or output by the user program. This is
done by interrogating or allocating the corresponding channel.
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US306

Table of Contents

Related product manuals