The module provides several diagnosis functions
Ä
Chapter 1.5.1.2.3.7 “Diagnosis”
on page 328.
Internal Data Exchange
Without the Fast Counter With the Fast Counter (only
with AC500)
Digital inputs (bytes) 4 6
Digital outputs (bytes) 2 4
Counter input data (words) 0 4
Counter output data (words) 0 8
I/O Configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or bus module) during power-up of the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max.
Module ID Internal 1200
1
)
Word 1200
0x04B0
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
Not for
FBP
Parameter
length
Internal 7 Byte 7-CPU
6-FBP
0 255 0x0Y02
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US326