EasyManua.ls Logo

ABB AC500 PLC - Output Ranges Voltage and Current

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range Pt100 /
Pt1000
-50...70 °C
Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
80.0 °C
:
70.1 °C
800
:
701
0320
:
02BD
Normal range 70.0 °C
:
0.1 °C
400.0 °C
:
:
:
0.1 °C
150.0 °C
:
:
0.1 °C
4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
0.0 °C 0.0 °C 0.0 °C 0 0000
Normal range -0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50,0 °C
-1
:
-500
FFFF
:
FE0C
Measured
value too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow < -60.0 °C < -60.0 °C < -60.0 °C -32768 8000
Output Ranges Voltage and Current
Range -10...+10 V 0...20 mA 4...20 mA Digital value
Decimal Hex.
Overflow 0 V 0 mA 0 mA > 32511 > 7EFF
Measured
value too high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
32511
:
27649
7EFF
:
6C01
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0,0007 mA
20.0000 mA
:
4.0006 mA
27648
:
1
6C00
:
0001
0.0000 V 0.0000 mA 4.0000 mA 0 0000
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
-1
-6912
-27648
FFFF
E500
9400
Device Specifications
Communication Interface Modules (S500) > Modbus
2019/04/173ADR010121, 13, en_US910

Table of Contents

Related product manuals