EasyManua.ls Logo

ABB AC500 PLC - Functionality; Electrical Connection

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functionality
Parameter Value
LED displays For signal states, errors and supply voltages
Internal power supply Via I/O bus
External power supply Via the terminals ZP, ZP3, ZP4, UP, UP3 and UP4
(process voltage 24 VDC)
Required terminal unit
TU542
Ä
Chapter 1.4.3 “TU515, TU516, TU516-H
and TU542 for I/O Modules” on page 153
The output module is plugged on the terminal unit TU542. Properly position the module and
press until it locks in place. The terminal unit is mounted on a DIN rail or with 2 screws plus the
additional accessory for wall mounting (TA526
Ä
Chapter 1.8.2.4 “TA526 - Wall Mounting
Accessory” on page 1152).
Electrical Connection
For a detailed description of the mounting, disassembly and electrical connec-
tion of the module, please refer to the System Assembly, Construction and Con-
nection chapter
Ä
Chapter 2.6 “AC500 (Standard)” on page 1248.
The electrical connection of the I/O channels is carried out using the 40 terminals of the I/O ter-
minal unit. I/O modules can be replaced without re-wiring the terminal units.
The terminals 1.8 to 2.8 and 1.9 to 2.9 are electrically interconnected within the I/O terminal unit
and always have the same assignment, irrespective of the inserted module:
Terminals 1.8 to 2.8: Process voltage UP = +24 VDC
Terminals 1.9 to 2.9: Process voltage ZP = 0 V
Terminal 3.8: Process voltage UP3 = +24 VDC
Terminal 3.9: Process voltage ZP3 = 0 V
Terminal 4.8: Process voltage UP4 = +24 VDC
Terminal 4.9: Process voltage ZP4 = 0 V
Terminals Signal Description
3.0, 3.1, 3.4, 3.5 O0 to O3 4 digital outputs
4.0, 4.1, 4.4, 4.5 O4 to O7 4 digital outputs
The internal power supply voltage for the module's circuitry is carried out via the I/O bus (pro-
vided by a bus Module or a CPU). Thus, the current consumption from 24 VDC power supply at
the terminals L+/UP and M/ZP of the CPU/bus module increases by 2 mA per DO526.
The external power supply connection is carried out via the UP, UP3, UP4 (+24 VDC) and the
ZP, ZP3, ZP4 (0 VDC) terminals.
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 363

Table of Contents

Related product manuals