EasyManua.ls Logo

ABB AC500 PLC - Connection of Passive-type Analog Sensors (Current) to the Analog Inputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.0
AI0+
2.1
AI1+
2.2
AI2+
2.3
AI3+
2.4
AI-
2.5
AO0+
2.6
AO1+
2.7
AO-
2.8
UP
2.9
ZP
24 V DC
-
+
-10 ... +10 V
0 ... +10 V
Fig. 123: Connection of active-type sensors (voltage) with no electrically isolated power supply
to the analog inputs
NOTICE!
Risk of faulty measurements!
The negative pole/earthing potential at the sensors must not have too large a
potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
Voltage 0...10 V 1 channel used
Voltage -10 V...+10 V 1 channel used
For the measuring ranges that can be configured, plese refer to the sections Measuring Ranges
Ä
Chapter 1.7.1.2.10 “Measuring Ranges” on page 731 and Parameterization
Ä
Chapter
1.7.1.2.7 “Parameterization” on page 721.
To avoid error messages, configure unused analog input channels as "unused".
Connection of Passive-type Analog Sensors (Current) to the Analog Inputs
The following figure shows the connection of passive-type analog sensors (current) to the
analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/173ADR010121, 13, en_US716

Table of Contents

Related product manuals