EasyManua.ls Logo

ABB AC500 PLC - 1.2.1.2.1 Intended Purpose

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Terminals of Onboard I/Os for PM55x-T Terminals of Onboard I/Os for PM55x-R and
PM55x-R-AC
AC500-eCo processor modules are equipped with non-removable terminals.
AC500-eCo processor modules are equipped with removable terminal blocks
which must be ordered separately.
The electrical functionality of both processor module types is identical.
1.2.1.2.1 Intended Purpose
The processor module PM55x provides 8 onboard digital inputs (24 VDC) and 6 onboard digital
outputs (depending on variant 24 VDC transistor outputs or relay outputs).
Numbers and types of the onboard I/Os are listed in the table below:
Processor
module
Power
supply
No. and type
of digital
inputs
No. and type
of digital out-
puts
No. and type
of analog
inputs
No. and type
of analog
outputs
PM55x-T(P),
PM55x-T(P)-
ETH
24 VDC 8 x 24 VDC 6 x 24 VDC,
0.5 A max.
(transistor)
none none
PM55x-R(P) 24 VDC 8 x 24 VDC 6 x relay
output, 2 A
max.
none none
PM55x-R(P)-
AC
120 to 240 V
AC
8 x 24 VDC 6 x relay
output, 2 A
max.
none none
All inputs (DI0...DI7) belong to 1 group. All outputs (DO0...DO5 / NO0...NO5) belong to 1
group. The inputs and outputs are group-wise electrically isolated.
Processor
Module PM55x
Device Specifications
Processor Modules > AC500-eCo
2019/04/173ADR010121, 13, en_US38

Table of Contents