NOTICE!
Risk of damaging the terminal base!
Excessive current might damage the clamp and terminal base.
Make sure that the current flowing through the removable clamps never
exceeds 8 A (with 1.5 mm
2
conductor).
Serial Interface COM1
Serial Interface Pin Signal Interface Description
Terminal
block
removed
Terminal
block
inserted
1 Terminator P RS-485 Terminator P
2 RxD/TxD-P RS-485 Receive/Transmit,
positive
3 RxD/TxD-N RS-485 Receive/Transmit,
negative
4 Terminator N RS-485 Terminator N
5 RTS RS-232 Request to send
(output)
6 TxD RS-232 Transmit data
(output)
7 SGND Signal Ground
8 RxD RS-232 Receive data
(input)
9 CTS RS-232 Clear to send
(input)
The serial interface COM1 is connected to a removable 9-pin terminal block. It is configurable
for RS-232 and RS-485.
NOTICE!
Unused connector!
Make sure that the terminal block is always connected to the terminal base,
even if you do not use the interface.
For a detailed description of COM1, please refer to Serial interface COM1
Ä
Chapter 2.6.4.6
“Serial Interface COM1 of the Terminal Bases” on page 1278.
Serial Interface COM2
The serial interface COM2 is connected to a D-sub 9. It is configurable for RS-232 and RS-485.
COM2 cannot be used for communication via CS31 System Bus. For a detailed
description of COM2, please refer to Serial interface COM2.
Ä
Chapter 2.6.4.7
“Serial Interface COM2 of the Terminal Bases ” on page 1280
Pin assignment
Processor Modules > AC500 (Standard)
2019/04/173ADR010121, 13, en_US84