Voltage -10 V...+10 V Load ±10 mA max. 1 channel used
The measuring ranges are described in the section Measuring Ranges
Ä
Chapter 1.7.2.2.8
“Parameterization” on page 794
Ä
Chapter 1.7.2.2.11 “Measuring Ranges” on page 802:
Unused analog outputs can be left open-circuited.
Connection of Analog Output Loads (Current)
The following figure shows the connection of output loads to the analog output AO0. Proceed
with the analog output AO1 in the same way.
Fig. 156: Connection of analog output loads (current)
Current 0...20 mA Load 0...500 W 1 channel used
Current 4...20 mA Load 0...500 W 1 channel used
The measuring ranges are described in the section Measuring Ranges
Ä
Chapter 1.7.2.2.8
“Parameterization” on page 794
Ä
Chapter 1.7.2.2.11 “Measuring Ranges” on page 802:
Unused analog outputs can be left open-circuited.
1.7.2.2.4 CS31 Bus Connections
The following figures show the different possibilities of connecting the CS31 buses to the CI592-
CS31:
Device Specifications
Communication Interface Modules (S500) > CS31
2019/04/173ADR010121, 13, en_US792