Parameter Value
Mounting position Horizontal or vertical with derating (output
load reduced to 50 % at 40 °C per group)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Technical Data of the Digital Inputs
Parameter Value
Number of channels per module 32
Distribution of the channels into groups 1 group of 32 channels
Terminals of the channels I0 to I7 1.0 to 1.7
Terminals of the channels I8 to I15 2.0 to 2.7
Terminals of the channels I16 to I23 3.0 to 3.7
Terminals of the channels I24 to I31 4.0 to 4.7
Reference potential for all inputs Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole
of the process supply voltage, signal name
ZP)
Galvanic isolation From the rest of the module (I/O bus)
Indication of the input signals One yellow LED per channel, the LED is ON
when the input signal is high (signal 1)
Monitoring point of input indicator LED is part of the input circuitry
Input type acc. to EN 61131-2 Type 1
Input delay (0 -> 1 or 1 -> 0) Typ. 8 ms, configurable from 0.1 to 32 ms
Input signal voltage 24 VDC
Signal 0 -3 V...+5 V
Undefined signal > +5 V...< +15 V
Signal 1 +15 V...+30 V
Ripple with signal 0 Within -3 V...+5 V
Ripple with signal 1 Within +15 V...+30 V
Input current per channel
Input voltage +24 V Typ. 5 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 5 mA
Input voltage +30 V < 8 mA
Max. cable length
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 351