EasyManua.ls Logo

ABB AC500 PLC - Functionality; Electrical Connection

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functionality
Parameter Value
LED displays For signal states
Internal power supply Via I/O bus
External power supply Via the terminal L+ (process voltage 24 VDC). The negative
pole is provided by the I/O bus.
Electrical Connection
For a detailed description of the mounting, disassembly and electrical connec-
tion of the module, please refer to the System Assembly chapter
Ä
Chapter 2.5
“AC500-eCo” on page 1192.
The electrical connection is carried out by using removable 9-pin and 11-pin terminal blocks.
These terminal blocks differ in their connection system (spring terminals or screw terminals,
cable mounting from the front or from the side). For more information, please refer to the
chapter Terminal Blocks for S500-eCo I/O Modules
Ä
Chapter 1.8.3.2 “TA563-TA565 - Terminal
Blocks” on page 1164. The terminal blocks are not included in the module's scope of delivery and
must be ordered separately.
The following block diagram shows the internal construction of the digital outputs:
NO212
NO111
R0..314
NO313
NO617
NO516
R4..719
NO718
NO010
NO415
L+20
Table 45: Assignment of the Terminals:
Terminal Signal Description
10 NO0 Normally-open contact of the output NO0
11 NO1 Normally-open contact of the output NO1
12 NO2 Normally-open contact of the output NO2
13 NO3 Normally-open contact of the output NO3
14 R0..3 Output common for signals NO0 to NO3
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US242

Table of Contents