Terminal 4.8: process supply voltage UP3 = +24 VDC
Terminals 2.9, 3.9 and 4.9: process supply voltage ZP = 0 V
For a detailed description of the mounting, disassembly and electrical connec-
tion of the module, please refer to the System Assembly, Construction and Con-
nection chapter
Ä
Chapter 2.6 “AC500 (Standard)” on page 1248.
With a separate UP3 power supply, the digital outputs can be switched off exter-
nally. This way, an emergency-off functionality can be realized.
Possibilities of Connection
The assignment of the 9-pin female D-sub connector for the CANopen signals
1
5
6
9
1 --- Reserved
2 CAN- Inverted signal of the CAN Bus
3 CAN_GND Ground potential of the CAN bus
4 --- Reserved
5 --- Reserved
6 --- Reserved
7 CAN+ Non-inverted signal of the CAN Bus
8 --- Reserved
9 --- Reserved
Shield Cable shield Functional earth
The ends of the data lines have to be terminated with a 120 W bus terminating resistor. The bus
terminating resistor is usually installed directly at the bus connector.
1
2
4
3
1
2
4
3
1
2
4
3
6 6 6
120
120
Node 1 Node 2 Node N
5 5
Fig. 130: CANopen interface, bus terminating resistors connected to the line ends
Mounting on
Terminal Units
TU509 or TU510
Bus Terminating
Resistors
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/17 3ADR010121, 13, en_US 741