EasyManua.ls Logo

ABB AC500 PLC - Intended Purpose; Functionality

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Terminal number
4 Allocation of signal name
5 Terminal block for input signals (9-pin)
6 Terminal block for output signals (11-pin)
7 2 holes for wall-mounting with screws
8 DIN rail
Intended Purpose
The device can be used as a decentralized I/O extension module for S500 Communication
Interface Modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN) or as a centralized
extension module for AC500 CPUs (PM5xx).
The inputs are not electrically isolated from each other.
The outputs are not electrically isolated from each other.
All other circuitry of the module is not electrically isolated from the inputs/outputs or from the I/O
bus.
The I/O module must not be used as a decentralized I/O module with CI590-
CS31-HA bus modules.
Functionality
4 analog inputs, individually configurable for
Not used (default)
-2.5 V...+2.5 V
-5 V...+ 5 V
0 V...+5 V
0 V...+10 V
0 mA...20 mA
4 mA...20 mA
2 analog outputs, individually configurable for
Not used (default)
-10 V...+10 V
0 mA...20 mA
4 mA...20 mA
Parameter Value
Resolution of the analog channels
Voltage bipolar (-2.5 V...+2.5 V; -5 V...+5 V) 11 bits plus sign
Voltage unipolar (0 V...5 V; 0 V...10 V) 12 bits
Current (0 mA...20 mA; 4 mA...20 mA) 12 bits
LED displays 2 LEDs for process voltage and error mes-
sages
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US438

Table of Contents

Related product manuals