1.7.2.3.8 I/O Configuration
The DC551-CS31 module does not store configuration data itself. The 16 configurable channels
are defined as inputs or outputs by the user program, i.e. each of the configurable channels can
be used as input or output (or re-readable output) by interrogation or allocation by the user pro-
gram.
1.7.2.3.9 Parameterization
No. Name Value Internal
value
Internal
value,
type
Default Min. Max.
1 Module ID Internal 2715
1
)
Word 2715
0x0a9b
0 65535
2 Ignore
module
No
Yes
0
1
Byte No
0x00
14 Parameter
length
Internal 8
(7
4
)
Byte 8
(7
4
)
0 255
16 Check
supply
Off
On
0
1
Byte On
0x01
17 Input
delay
0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
Byte 8 ms
0x02
18 Fast
counter
0
:
10
3
)
0
:
10
Byte Mode 0
0x00
Nr.+1 Detection
short-cir-
cuit at out-
puts
Off
On
0
1
Byte On
0x01
Nr.+1 Behaviour
outputs at
communi-
cation
errors
Off
Last value
Substitute
value
0
1
2
Byte Off
0x00
Nr.+1 Substitute
value out-
puts
Bit 15 =
Output 15
Bit 0 =
Output 0
0...65535 0...0xffff Word 0
1
) With CS31 and addresses less than 70, the value is increased by 1
3
) Counter operating modes
Ä
Chapter 1.5.1.2.10 “Fast Counter” on page 394, description of
the Fast Counter
Ä
Chapter 1.5.1.2.10 “Fast Counter” on page 394
4
) With CS31 and addresses less than 70, without the parameter Fast Counter
Device Specifications
Communication Interface Modules (S500) > CS31
2019/04/173ADR010121, 13, en_US818