EasyManua.ls Logo

ABB AC500 PLC - Output Ranges Voltage and Current

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range Digital value
Decimal Hex.
0 0000
-1
:
-500
FFFF
:
FE0C
Measured value too low -501
:
-600
FE0B
:
FDA8
Underflow -32768 8000
Output Ranges Voltage and Current
Range -10...+10 V 0...20 mA 4...20 mA
Overflow > 11.7589 V > 23.5178 mA > 22.8142 mA
Measured value too
high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0.0007 mA
20.0000 mA
:
4.0006 mA
0.0000 V 0.0000 mA 4.0000 mA
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
Measured value too
low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
Underflow < -11.7589 V 0 mA 0 mA
Range Digital value
Decimal Hex.
Overflow > 32511 > 7EFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range 27648
:
1
6C00
:
0001
0 0000
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/17 3ADR010121, 13, en_US 1039

Table of Contents