EasyManua.ls Logo

ABB AC500 PLC - Output Ranges Voltage and Current; 1.7.5.1.11 Technical Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Output Ranges Voltage and Current
Range -10...+10 V 0...20 mA 4...20 mA
Overflow >11.7589 V >23.5178 mA >22.8142 mA
Measured value too
high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0.0007 mA
20.0000 mA
:
4.0006 mA
0.0000 V 0.0000 mA 4.0000 mA
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
Measured value too
low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
Underflow 0 V 0 mA 0 mA
Range Digital value
Decimal Hex.
Overflow > 32511 > 7EFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range 27648
:
1
6C00
:
0001
0 0000
-1
-6912
-27648
FFFF
E500
9400
Measured value too low -27649
:
-32512
93FF
:
8100
Underflow < -32512 < 8100
The represented resolution corresponds to 16 bits.
1.7.5.1.11 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/173ADR010121, 13, en_US974

Table of Contents