1.3.7.2.3 State LEDs
The PROFIBUS state is shown by state LEDs.
Table 32: Meaning of the diagnosis LEDs
LED Color State Description
PWR Green ON (light) Power supply available
OFF (dark) Power supply not available or defective
hardware
RDY Yellow ON Boot procedure
Blinking Boot failure
OFF ---
RUN Green ON Communication module is operational
Blinking ---
OFF Communication module is not operational
STA Green ON Communication to all slaves is established
Flashes cyclic ---
Flashes non-
cyclic
No configuration or stack error
OFF No communication
ERR Red ON Communication to one/all slaves is dis-
connected
Flashes cyclic Communication to at least one slave is
disconnected
OFF No error
STA Yellow Blinking
(synchronously)
No production data available,
no bus communication possible.
ERR Yellow
LED state
during
firmware
update
STA Green Blinking
(synchronously)
Firmware file transfers during
communication module firmware update.
ERR Red
STA Green Blinking
(alternately)
Communication module writes the
firmware file to the internal flash.
Do not power off the PLC!
ERR Red
1.3.7.2.4 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Device Specifications
Communication Modules (AC500 Standard) > PROFIBUS
2019/04/17 3ADR010121, 13, en_US 131