State LEDs
LED State Color LED = OFF LED = ON
Outputs
O0...O7
Digital output Yellow Output is
OFF
Output is ON
Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Galvanic isolation Yes, between the channels and the rest of the
module
Isolated groups 8 (1 channel per group)
Current consumption from 24 VDC power
supply at the L+/UP and M/ZP terminals of the
CPU/Bus Module
Ca. 10 mA
Max. power dissipation within the module On Request
Weight ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switch-gear cabinet.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical Data of the Digital Outputs
Parameter Value
Number of channels per module 8 triac outputs
Distribution of the channels into groups 8 groups (1 channel per group)
Connection of the channels O0 to O7 Terminals 1, 3, 5, 7, 10, 12, 14, 16
Reference potential for the channels O0 to O7 Terminals 2, 4, 6, 8, 11, 13, 15, 17
Output voltage for signal 1 On Request
Max. leakage current with signal 0 1.1 mA root mean square at 132 VAC and
1.8 mA root mean square at 264 VAC
Output voltage
Rated value 120 VAC or 240 VAC
Indication of the output signals 1 yellow LED per channel; the LED is on
when the output signal is high (signal 1) and
the module is powered via the I/O bus
No effects of
multiple over-
loads
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US258