If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Name Value Internal
Value
Internal
Value,
Type
Default Min. Max. EDS Slot
Index
Module ID Internal
6135
1
)
WORD 6135
0x17F7
0 65535 xx01
Ignore
module
No
Yes
0
1
BYTE No
(0x00)
Parameter
length
Internal 1 BYTE 0 0 255
xx02
2
)
1
) with CS31 and addresses smaller than 70, the value is increased by 1
2
) Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n)
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
(0) =
0x03
0xF8, 0x17, 0x00,\
0x01;
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 279