PWM/pulse outputs 2 pulse-width-modulators or pulse outputs
Output specification
- Push-pull output: 24 VDC, 100 mA max.
- Current limitation (thermal and over current)
PWM specification
- Frequency from 1 Hz to 100 kHz
- Value from 0 to 100 %
Pulse specification
- Frequency from 1 Hz to 15 kHz
- Pulse emission from 1 to 65535 pulses
- Number of pulses emitted indicator (0 to 100 %)
Frequency specification
- Frequency output = 100 kHz when duty cycle set to 50 %
Power supply for encoders 2 5V power supplies, max. 100 mA
LED displays For signal states, errors and supply voltage
Internal power supply Via I/O bus
External power supply Via the terminals UP (process voltage 24 VDC) and ZP (0
VDC)
Required Terminal Unit
TU515 or TU516
Ä
Chapter 1.4.3 “TU515, TU516, TU516-H
and TU542 for I/O Modules” on page 153
1.6.2.1.3 Electrical Connection
The function module CD522 can be connected to the following devices via the I/O bus con-
nector:
CS31 bus module DC551-CS31
Processor module PM5xx
Other AC500 I/O devices.
The electrical connection is carried out by using the 40 terminals of the Terminal Unit TU515/
TU516
Ä
Chapter 1.4.3 “TU515, TU516, TU516-H and TU542 for I/O Modules” on page 153.
Table 93: Assignment of the terminals
Terminal Signal Description
1.0 /A0 Inverted input signal A of encoder 0
1.1 /B0 Inverted input signal B of encoder 0
1.2 /Z0 Inverted input signal Z of encoder 0
1.3 5V0 +5 VDC power supply output 0 for sensors
1.4 0V 0 V reference input
1.5 O0 Output signal of the fast output O0
1.6 0V 0 V reference input
1.7 O1 Output signal of the fast output O1
1.8 UP Process voltage UP (24 VDC)
1.9 ZP Process voltage ZP (0 VDC)
Device Specifications
Function Modules > S500