Range Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Measured value
too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow < -60.0 °C < -60.0 °C -32768 8000
Output Ranges Voltage and Current
Range -10...+10 V 0...20 mA 4...20 mA Digital value
Decimal Hex.
Overflow 0 V 0 mA 0 mA > 32511 > 7EFF
Measured
value too high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
32511
:
27649
7EFF
:
6C01
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0,0007 mA
20.0000 mA
:
4.0006 mA
27648
:
1
6C00
:
0001
0.0000 V 0.0000 mA 4.0000 mA 0 0000
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
-1
-6912
-27648
FFFF
E500
9400
Measured
value too low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
-27649
:
-32512
93FF
:
8100
Underflow 0 V 0 mA 0 mA < -32512 < 8100
The represented resolution corresponds to 16 bits.
1.7.3.1.11 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Bus connection 2 x RJ45
Technology Hilscher netX100
Transfer rate 10/100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEE802.3
Device Specifications
Communication Interface Modules (S500) > EtherCAT
2019/04/17 3ADR010121, 13, en_US 853