1.7.6.3.2 Functionality
The CI502 Bus Module contains 24 I/O channels with the following properties:
8 digital configurable inputs/outputs
8 digital inputs: 24 VDC
8 digital outputs: 24 VDC, 0.5 A max.
The inputs/outputs are electrically isolated from the Ethernet network. There is no potential sep-
aration between the channels. The configuration of the analog inputs/outputs is performed by
software.
Parameter Value
Interface Ethernet
Protocol PROFINET IO RT
Power supply From the process supply voltage UP
Supply of the electronic circuitry of the I/O
expansion modules attached
Through the expansion bus interface (I/O bus)
Rotary switches For setting the IO device identifier for configura-
tion purposes (00h to FFh)
Configurable digital inputs/outputs 8 (configurable via software)
Digital inputs 8 (24 VDC; delay time configurable via soft-
ware)
Digital outputs 8 (24 VDC, 0.5 A max.)
LED displays For system displays, signal states, errors and
power supply
External supply voltage Via terminals ZP, UP and UP3 (process supply
voltage 24 VDC)
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to
35 V
Required terminal unit
TU507-ETH or TU508-ETH
Ä
Chapter 1.4.1
“TU507-ETH and TU508-ETH for Ethernet
Communication Interface Modules”
on page 145
1.7.6.3.3 Electrical Connection
The Ethernet bus module CI502-PNIO is plugged on the I/O terminal unit TU507-ETH
Ä
Chapter 1.4.1 “TU507-ETH and TU508-ETH for Ethernet Communication Interface Modules”
on page 145 or TU508-ETH
Ä
Chapter 1.4.1 “TU507-ETH and TU508-ETH for Ethernet Com-
munication Interface Modules” on page 145. Properly seat the module and press until it locks in
place. The terminal unit is mounted on a DIN rail or with 2 screws plus the additional accessory
for wall mounting (TA526
Ä
Chapter 1.8.2.4 “TA526 - Wall Mounting Accessory” on page 1152).
The electrical connection of the I/O channels is carried out using the 30 terminals of the I/O ter-
minal unit. I/O modules can be replaced without re-wiring the terminal units.
For a detailed description of the mounting, disassembly and electrical connec-
tion of the module, please refer to the System Assembly, Construction and Con-
nection chapter
Ä
Chapter 2.6 “AC500 (Standard)” on page 1248.
The terminals 1.8 and 2.8 as well as 1.9, 2.9 and 3.9 are electrically interconnected within the
terminal unit and have always the same assignment, independent of the inserted module:
Terminals 1.8 and 2.8: Process supply voltage UP = +24 VDC
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1048