ABB AC500 PLC - Technical Data of the Fast Counter

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Output short circuit protection Should be provided externally with a fuse or circuit
breaker
Rated protection fuse 6 A gL/gG per channel
Min. switching current 10 mA
Output switching capacity
Resistive load, max. 3 A; 3 A (230 VAC), 2 A (24 VDC)
Inductive load, max. 1.5 A; 1.5 A (230 VAC), 1.5 A (24 VDC)
Lamp load 60 W (230 VAC), 10 W (24 VDC)
Output switching capacity (XC ver-
sion above 60 °C)
On request
Life time (cycles) Mechanical: 300 000;
Under load: 300 000 (24 VDC at 2 A), 200 000 (120
VAC at 2 A), 100 000 (230 VAC at 3 A)
Spark suppression with inductive AC
load
Must be performed externally according to driven load
specifications
Demagnetization with inductive DC
load
A free-wheeling diode must be circuited in parallel to
the inductive load
Switching frequency
With resistive load Max. 10 Hz
With inductive load Max. 2 Hz
With lamp load On request
Max. cable length
Shielded 1000 m
Unshielded 600 m
Technical Data of the Fast Counter
The fast counter of the module does not work if the module is connected to a
FBP interface module
CS31 bus module
CANopen bus module
Parameter Value
Used inputs I0 / I1
Used outputs None
Counting frequency 50 kHz max.
Detailed description See Fast Counter
Operating modes See Operating modes
Device Specifications
I/O Modules > Digital I/O Modules