EasyManua.ls Logo

ABB AC500 PLC - Parameterization; Input Channel (2 x)

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Name Value Internal
value
Internal
value,
Type
Default Min. Max. EDS Slot
Index
Module ID Intern
6505
1
)
WORD 0x1969 0 65535 xx01
Ignore
module
No
Yes
0
1
BYTE No
0x00
Parameter
length
Intern 4 BYTE 0 0 255
xx02
2
)
Check
Supply
Off
On
0
1
BYTE On
0x01
Analog
Data
Format
Default 0 BYTE Default
0x00
255
1
) with CS31 and addresses less than 70, the value is increased by 1
2
) Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n)
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
0x07
0x6A, 0x19, 0x04, \
0x01, 0x00, \
0x00, 0x00;
Input Channel (2x)
Name Value Internal
value
Internal
value, Type
Default Min. Max.
Channel
configura-
tion
see table
2
) see table
2
)
BYTE 0
0x00 see
table
3
)
0 65535
Table 53: Channel Configuration
2
)
Internal value Operating modes for the analog inputs,
individually configurable
0 Not used (default)
3
)
8 2-wire Pt100 -50 °C...+400 °C
9 3-wire Pt100 -50 °C...+400 °C
16 2-wire Pt1000, -50 °C...+400 °C
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US410

Table of Contents

Related product manuals