Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Name Value Internal
value
Internal
value,
Type
Default Min. Max. EDS Slot
Index
Module ID Intern
6505
1
)
WORD 0x1969 0 65535 xx01
Ignore
module
No
Yes
0
1
BYTE No
0x00
Parameter
length
Intern 4 BYTE 0 0 255
xx02
2
)
Check
Supply
Off
On
0
1
BYTE On
0x01
Analog
Data
Format
Default 0 BYTE Default
0x00
255
1
) with CS31 and addresses less than 70, the value is increased by 1
2
) Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n)
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
0x07
0x6A, 0x19, 0x04, \
0x01, 0x00, \
0x00, 0x00;
Input Channel (2x)
Name Value Internal
value
Internal
value, Type
Default Min. Max.
Channel
configura-
tion
see table
2
) see table
2
)
BYTE 0
0x00 see
table
3
)
0 65535
Table 53: Channel Configuration
2
)
Internal value Operating modes for the analog inputs,
individually configurable
0 Not used (default)
3
)
8 2-wire Pt100 -50 °C...+400 °C
9 3-wire Pt100 -50 °C...+400 °C
16 2-wire Pt1000, -50 °C...+400 °C
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US410