Parameter Value
Relationship between input signal and hex
code
See
Ä
Chapter 1.7.1.2.10.3 “Output Ranges
Voltage and Current” on page 732
Unused outputs Are configured as "unused" (default value) and
can be left open-circuited
Technical Data of the Fast Counter
Parameter Value
Used inputs Terminal 3.0 (DI0), 3.1 (DI1)
Used outputs Terminal 4.0 (DO0)
Counting frequency Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Detailed description
Fast Counter
Ä
Chapter 1.5.1.2.10 “Fast
Counter” on page 394
Operating modes
Operating modes
Ä
Chapter 1.5.1.2.10 “Fast
Counter” on page 394
1.7.1.2.12 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 228 100
R0001
CI581-CN, CANopen bus module with
8 DI, 8 DO, 4 AI and 2 AO
Active
1SAP 428 100
R0001
CI581-CN-XC, CANopen bus module
with 8 DI, 8 DO, 4 AI and 2 AO,
XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.7.1.3 CI582-CN
8 digital inputs 24 VDC
8 digital outputs 24 VDC, 0.5 A max.
8 configurable digital inputs/outputs 24 VDC, 0.5 A max.
Module-wise electrically isolated
Fast counter
XC version for use in extreme ambient conditions available
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/17 3ADR010121, 13, en_US 737