Only additional details are therefore documented below.
Technical Data of the Module
Parameter Value
Process supply voltages UP/UP3
Rated value 24 VDC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Electrical isolation Ethernet interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.15 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 1.8 and 2.8 for +24 V (UP)
Terminal 3.8 for +24 V (UP3)
Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of configurable digital inputs/outputs 8
Input data length 12 bytes
Output data length 20 bytes
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Setting of the IO Device identifier With 2 rotary switches at the front side of the
module
Diagnosis
See Diagnosis and Displays
Ä
Chapter
1.7.6.3.8 “Diagnosis” on page 1057
Operation and error displays 34 LEDs (totally)
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
Extended ambient temperature (XC version) > 60 °C on request
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Communication Interface Modules (S500) > PROFINET
2019/04/17 3ADR010121, 13, en_US 1063