EasyManua.ls Logo

ABB AC500 PLC - Parameterization

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max. Max.
Module ID Internal 1101
1
)
WORD 1101
0x044D
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
BYTE No
0x00
not for
FBP
Parameter
length
Internal 7 BYTE 7-CPU
7-FBP
0 255 0x0Y02
Check
supply
Off
on
0
1
BYTE On
0x01
0 1 0x0Y03
Output
short cir-
cuit detec-
tion
Off
On
0
1
BYTE On
0x01
0 1 0x0Y04
Behaviour
of outputs
at com-
munica-
tion errors
Off
Last value
Substitute
value
0
1+(n*5)
2+(n*5),
n £ 2
BYTE Off
0x00
0 2 0x0Y05
Substitute
value at
outputs
Bit 31 =
Output 31
Bit 0 =
Output 0
0...
42949672
95
0...
0xffffffff
DWORD 0
0x000000
00
0 42949672
95
0x0Y06
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
10
0x04, 0x4d, 0x07, \
0x01, 0x01, 0x00, 0x00, 0x00, 0x00, 0x00;
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US356

Table of Contents