EasyManua.ls Logo

ABB AC500 PLC - Diagnosis; State LEDs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnosis
E1...E4 d1 d2 d3 d4 Identifier
000...063
AC500-
Display
<− Display in
Class Comp Dev Mod Ch Err PS501
PLC
Browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
PNIO
diagnosis
block
Class Interface Device Module Channel Error
Identifier
Error message Remedy
1
)
2
)
3
)
4
)
3 14 1...10 31 31 19 Checksum error in the
I/O module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 43 Internal error in the
module
Replace
I/O module
11 / 12 ADR 1...10
3 14 1...10 31 31 9 Overflow diagnosis
buffer
Restart
11 / 12 ADR 1...10
3 14 1...10 31 31 26 Parameter error Check
master
11 / 12 ADR 1...10
Remarks:
Param-
eter
Remark
1
)
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31-Bus), 12 = COM2.
The PNIO diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself, 1...10 = decentralized communication interface module 1...10,
ADR = hardware address (e.g. of the DC551-CS31)
3
)
With "Module" the following allocation applies depending on the master:
module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 = expan-
sion 1...10
4
)
In case of module errors, with channel "31 = module itself" is output.
State LEDs
LED State Color LED = OFF LED = ON
Inputs I0...I15 Digital input Yellow Input is OFF Input is ON
(the input voltage is
only displayed if the
supply voltage of the
module is ON)
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US220