Measuring Ranges
Input Ranges of Voltage, Current and Digital Input
Range 0...10
V
-10...+10
V
0...20
mA
4...20
mA
Digital
input
Digital value
Decimal Hex.
Overflow >11.7589 >11.7589 >23.5178 >22.8142 32767 7FFF
Measured
value too
high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
:
6C01
Normal
range
Normal
range or
measured
value too
low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
ON
27648
:
1
6C00
:
0001
0.0000 0.0000 0 4 OFF 0 0000
-0.0004
-1.7593
-0.0004
:
:
:
-10.0000
3.9994 -1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Underflow < -1.7593 <-11.7589 <0.0000 <1.1858 -32768 8000
The represented resolution corresponds to 16 bits.
Input Ranges Resistance
The resolution corresponds to 16 bits.
Range Pt100 / Pt
1000
-50...70 °C
Pt100 /
Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Overflow > 80.0 °C > 450.0 °C > 160.0 °C 32767 7FFF
Measured
value too high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
80.0 °C
:
70.1 °C
800
:
701
0320
:
02BD
Device Specifications