EasyManua.ls Logo

ABB AC500 PLC - Use of Analog Inputs as Digital Inputs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAUTION!
The earthing potential at the sensors must not have a too big potential differ-
ence with respect to ZP (max. ±1 V within the full signal range). Otherwise prob-
lems can occur concerning the common-mode input voltages of the involved
analog inputs.
UP
ZP
1.0
I0-
1.1
I1-
1.8
UP
1.9
ZP
PTC
2.0
I0+
2.1
I1+
2.8
UP
2.9
ZP
0 ... 10 V
-10 ... +10 V
+
-
U
IN
Fig. 39: Connection example
The negative pole of the sensor must be earthed next to the sensor.
The following measuring ranges can be configured
Ä
Chapter 1.5.2.2.1.6 “Parameterization”
on page 463
Ä
Chapter 1.5.2.2.1.9 “Measuring Ranges” on page 468:
Voltage 0 V...10 V with differential inputs, 2 chan-
nels used
Voltage -10 V...+10 V with differential inputs, 2 chan-
nels used
The function of the LEDs is described under Displays
Ä
Chapter 1.5.2.2.1.7 “Diagnosis”
on page 466.
In order to avoid error messages or long processing times, it is useful to configure unused
analog input channels as "unused".
Use of Analog Inputs as Digital Inputs
Several (or all) analog inputs can be configured as digital inputs The inputs are not electrically
isolated against the other analog channels.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 461

Table of Contents

Related product manuals