ABB AC500 PLC - 2.5.1.2 Creepage Distances and Clearances; 2.5.1.3 Insulation Test Voltages, Routine Test

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
DC supply Interruption < 10 ms, time between 2 interruptions
> 1 s, PS2
AC supply Interruption < 0.5 periods, time between 2 inter-
ruptions > 1 s
NOTICE!
Exceeding the maximum power supply voltage (> 30 VDC) for process or
supply voltages could lead to unrecoverable damage of the system. The system
could be destroyed.
Parameter Value
Temperature
Operating 0 °C...+60 °C (horizontal mounting of modules)
0 °C...+40 °C (vertical mounting of modules and
output load reduced to 50 % per group)
Storage -40 °C...+70 °C
Transport -40 °C...+70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
2.5.1.2 Creepage Distances and Clearances
The creepage distances and clearances meet the requirements of the overvoltage category II,
pollution degree 2.
2.5.1.3 Insulation Test Voltages, Routine Test
Parameter Value
200 V...240 V circuits against
other circuitry
2500 V 1.2/50 µs
100 V...127 V circuits against
other circuitry
1500 V 1.2/50 µs
100 V...240 V circuits against
other circuitry
2500 V 1.2/50 µs
24 V circuits (supply, 24 V
inputs/outputs, analogue
inputs/outputs ), if they are
electrically isolated against
other circuitry
500 V 1.2/50 µs
COM interfaces, electrically
isolated
500 V 1.2/50 µs
According to EN
61131-2
System Assembly, Construction and Connection
AC500-eCo > System Data AC500-eCo
2019/04/17 3ADR010121, 13, en_US 1193