ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of analog inputs 4
Number of analog outputs 2
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Setting of the PROFIBUS DP identifier With 2 rotary switches at the front side of the
module
Diagnose
See Diagnosis
Ä
Chapter 1.7.5.2.8 “Diagnosis”
on page 992
Operation and error displays 34 LEDs (totally)
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical Data of the Digital Inputs
Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Terminals of the channels DI0 to DI7 Terminals 3.0 to 3.7
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/17 3ADR010121, 13, en_US 999