Parameter Value
Relationship between input signal and hex
code
Table Output ranges voltage and current
Ä
Chapter 1.7.4.1.9.3 “Output Ranges Voltage
and Current” on page 910
Unused outputs Are configured as "unused" (default value) and
can be left open-circuited
Technical Data of the Fast Counter
Parameter Value
Used inputs Terminal 2.0 (DI0), 2.1 (DI1)
Used outputs Terminal 3.0 (DO0)
Counting frequency Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Detailed description See Fast Counter
Operating modes See Operating modes
1.7.4.1.11 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 222 100 R0001 CI521-MODTCP, Modbus TCP bus
module, 4 AI, 2 AO, 8 DI and 8 DO
Active
1SAP 422 100 R0001 CI521-MODTCP-XC, Modbus TCP
bus module, 4 AI, 2 AO, 8 DI and
8 DO, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
1.7.4.2 CI522-MODTCP
8 digital inputs 24 VDC
8 digital outputs 24 VDC, 0.5 A max.
8 configurable digital inputs/outputs 24 VDC, 0.5 A max.
Module-wise electrically isolated
Fast Counter
XC version for usage in extreme ambient conditions available
Device Specifications
Communication Interface Modules (S500) > Modbus
2019/04/173ADR010121, 13, en_US916