ABB AC500 PLC - Measuring Ranges; Input Ranges of Voltage, Current and Digital Input

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED State Color LED = OFF LED = ON LED flashes
Inputs
I0...I7
Analog input Yellow Input is OFF Input is ON
(brightness
depends on
the value of
the analog
signal)
--
Outputs
O0...O7
Analog
output
Yellow Output is
OFF
Output is ON
(brightness
depends on
the value of
the analog
signal)
--
UP Process
voltage
24 VDC via
terminal
Green Process
voltage is
missing
Process
voltage OK
--
CH-ERR2 Channel
error, error
messages in
groups
(analog
inputs or out-
puts com-
bined into the
groups 2 and
4)
Red No error or
process
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
group
CH-ERR4 Red
CH-ERR *) Module error Red -- Internal error --
*) Both LEDs (CH-ERR2 and CH-ERR4) light up together
Measuring Ranges
Input Ranges of Voltage, Current and Digital Input
The represented resolution corresponds to 16 bits.
Range 0...10 V -10...+10 V 0...20 mA 4...20 mA Digital input
Overflow >11.7589 >11.7589 >23.5178 >22.8142
Measured
value too high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
Normal range
Normal range
or measured
value too low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
ON
0.0000 0.0000 0 4 OFF
-0.0004
-1.7593
-0.0004
:
:
:
-10.0000
3.9994
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US562