Table 157: Table Operation modes of analog outputs:
Internal value Operating modes of the analog outputs,
individually configurable
0 (default) Not used
128 -10 V...+10 V
129 0 mA...20 mA
130 4 mA...20 mA
Table 158: Table channel monitoring:
Internal value Check channel
0 Plausib(ility), cut wire, short circuit
3 None
Table 159: Table Substitute value:
Intended behaviour of
output channel when the
control system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF Off 0
Last value infinite Last value 0
Last value for 5 s and then
turn off
Last value 5 sec 0
Last value for 10 s and then
turn off
Last value 10 sec 0
Substitute value infinite Substitute value depending on configuration
Substitute value for 5 s and
then turn off
Substitute value 5 sec depending on configuration
Substitute value for 10 s and
then turn off
Substitute value 10 sec depending on configuration
Group Parameters for the Digital Part
Name Value Internal value Internal value,
type
Default
Input delay 0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE 0.1 ms
0x00
Detect short cir-
cuit at outputs
Off
On
0
1
BYTE On
0x01
Channel Config-
uration
Channel Moni-
toring
Substitute Value
Device Specifications
Communication Interface Modules (S500) > PROFIBUS
2019/04/173ADR010121, 13, en_US964