EasyManua.ls Logo

ABB AC500 PLC - Input Ranges Resistance

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range 0...10 V -10...+10 V 0...20 mA 4...20 mA Digital input
Measured
value too low
-10.0004
:
-11.7589
Underflow <-1.7593 <-11.7589 <0.0000 <1.1858
Range Digital value
Decimal Hex.
Overflow 32767 7FFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range
Normal range or measured value too
low
27648
:
1
6C00
:
0001
0 0000
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured value too low -27649
:
-32512
93FF
:
8100
Underflow -32768 8000
Input Ranges Resistance
Range Pt100 / Pt 1000
-50...70 °C
Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Overflow > 80.0 °C > 450.0 °C > 160.0 °C
Measured value too
high
450.0 °C
:
400.1 °C
160.0 °C
:
150.1 °C
80.0 °C
:
70.1 °C
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 563

Table of Contents