For further information regarding wiring and cable types see chapter Ethernet
Ä
Chapter 2.6.4.10 “Ethernet Connection Details” on page 1288.
1.7.6.4.5 Addressing
The module reads the position of the rotary switches only during power-up, i. e.
changes of the switch position during operation will have no effect until the next
module initialization.
1.7.6.4.6 Parameterization
Parameters of the Module
Name Value Internal value Internal value,
type
Default
Module ID
1
)
Internal 7010 WORD 7010
Parameter length Internal 33 BYTE 33
Error LED / Fail-
safe function
see table
2
)
On 0 BYTE 0
Off by E4 1
Off by E3 3
On + failsafe 16
Off by E4 + fail-
safe
17
Off by E3 + fail-
safe
19
Remarks:
1
) With a faulty module ID, the module reports a "parameter error" and does not perform cyclic
process data transmission
Table 181: Error LED / Failsafe function
2
)
Setting Description
On Error LED lights up at errors of all error classes, Failsafe-mode
off
Off by E4 Error LED lights up at errors of error classes E1, E2 and E3,
Failsafe-mode off
Off by E3 Error LED lights up at errors of error classes E1 and E2, Fail-
safe-mode off
On + Failsafe Error LED lights up at errors of all error classes, Failsafe-mode
on
Off by E4 + Failsafe Error LED lights up at errors of error classes E1, E2 and E3,
Failsafe-mode on
Off by E3 + Failsafe Error LED lights up at errors of error classes E1 and E2, Fail-
safe-mode on
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1074