ABB AC500 PLC - 1.7.3.2.11 Technical Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LED Color OFF ON Flashing
DO8 to DO15 Yellow Output is OFF Output is ON --
UP Green Process supply
voltage missing
Process supply
voltage OK and
initialization fin-
ished
--
UP3 Green Process supply
voltage missing
Process supply
voltage OK
--
CH-ERR1 to CH-
ERR3
Red No error or
process supply
voltage missing
Internal error Error on one
channel of the
corresponding
group
1.7.3.2.11 Technical Data
The System Data of AC500 and S500
Ä
Chapter 2.6.1 “System Data AC500” on page 1248 are
valid for standard version.
The System Data of AC500-XC
Ä
Chapter 2.7.1 “System Data AC500-XC” on page 1309 are
valid for the XC version.
Only additional details are therefore documented below.
Parameter Value
Bus connection 2 x RJ45
Technology Hilscher netX100
Transfer rate 10/100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEE802.3
Ethernet 100 base-TX, internal switch, 2x RJ45 socket
Expandability (S500 I/O Modules) Up to 10 S500 I/O Modules (Index C0 and
above), Not available(Index below C0)
Indicators 5 LEDs for state indication
Adjusting elements 2 rotary switches (used for future topology
extensions)
Quantity of input/output data CI512-ETHCAT: 10 bytes input and 14 bytes
output
CI511-ETHCAT: 18 bytes input and 18 bytes
output
Acyclic services SDO (1500 bytes max.)
Emergency ECAT_SLV_DIAG
Protective functions (according to COD-
ESYS)
Protected against:
short circuit
reverse supply
overvoltage
reverse polarity
Electrical isolation to network
Device Specifications
Communication Interface Modules (S500) > EtherCAT
2019/04/17 3ADR010121, 13, en_US 871