4 Allocation of signal name
5 Terminal block for input signals (9-pin)
6 Terminal block for input signals (11-pin)
7 2 holes for wall-mounting with screws
8 DIN rail
Intended Purpose
The device can be used as a decentralized I/O extension module for S500 Communication
Interface Modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN) or as a centralized
extension module for AC500 CPUs (PM5xx).
The inputs are group-wise electrically isolated from each other.
The other electronic circuitry of the module is electrically isolated from the inputs.
The I/O module must not be used as a decentralized I/O module with CI590-
CS31-HA bus modules.
Functionality
4 analog TC inputs, individually configurable for
Not used (default)
Voltage -80 mV ... + 80 mV
Thermocouple J-type -210 °C...+1200 °C
Thermocouple K-type -270 °C...+1372 °C
Thermocouple R-type -50 °C...+1768 °C
Thermocouple S-type -50 °C...+1768 °C
Thermocouple T-type -270 °C...+400 °C
Thermocouple E-type -270 °C...+1000 °C
Thermocouple N-type -270 °C...+1300 °C
Parameter Value
Resolution of the analog channels
Temperature 0.1 °C
LED displays 2 LEDs for process voltage and error mes-
sages
Internal supply Via I/O bus
External supply Via the terminals UP (process voltage 24 VDC)
and ZP (0 VDC)
Electrical Connection
For a detailed description of the mounting, disassembly and electrical connec-
tion of the module, please refer to the System Assembly chapter
Ä
Chapter 2.5
“AC500-eCo” on page 1192.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 417