EasyManua.ls Logo

ABB AC500 PLC - 1.3.4.1.5 Ordering Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Usable CPUs
PM57x, PM58x, PM59x
Ä
Chapter 1.2.2.1
“PM57x (-y), PM58x (-y) and PM59x (-y)”
on page 65
Usable terminal bases
All TB5xx
Ä
Chapter 1.1.1 “TB51x-TB54x”
on page 4
Bus connection Pluggable connector COMBICON, 2x5-pin
Internal power supply Via the communication module Interface of the
terminal base
Transfer rate 10 kbit/s to 1 Mbit/s
Transfer method According to CAN standard
Bus length (segment length max.) According to table: Maximum cable length
within a CANopen field bus
Indicators 5 LEDs
Current consumption from 24 VDC power
supply at the terminal base of the CPU
Typ. 65 mA
Weight Ca. 150 g
Ambient temperature see:
System data AC500
Ä
Chapter 2.6.1 “System
Data AC500” on page 1248
System Data AC500-XC
Ä
Chapter 2.7.1
“System Data AC500-XC” on page 1309
Adjusting elements None
Quantity of input and output data per I/O
device
Max. 512 byte (respectively for input and
output)
Supported protocol services NMT slave
PDO
SDO server
Heartbeat
Nodeguard
Min. bus cycle 1 ms
1.3.4.1.5 Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 172 800 R0001 CM588-CN, communication module
CANopen slave
Active
1SAP 372 800 R0001 CM588-CN-XC, communication
module CANopen slave, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.
Device Specifications
Communication Modules (AC500 Standard) > CANopen
2019/04/17 3ADR010121, 13, en_US 109

Table of Contents