The function of the LEDs is described under Diagnosis and displays / displays
Ä
Chapter
1.5.2.2.2.7 “Diagnosis” on page 493.
In order to avoid error messages or long processing times, it is useful to configure unused
analog input channels as "unused".
Connection of Active-type Analog Sensors (Voltage) with no Electrically Isolated Power Supply
Fig. 44: Connection example
CAUTION!
If GND is not directly connected to ZP at the sensor, the supply current flows via
the GND line to ZP. Measuring errors can only occur caused by voltage differ-
ences higher than ±20 VDC between GND and ZP.
The measuring ranges can be configured
Ä
Chapter 1.5.2.2.2.6 “Parameterization”
on page 489 :
Voltage -50 mV...+50 mV 1 channel used
Voltage -500 mV...+500 mV 1 channel used
Voltage -1 V...+1 V 1 channel used
Voltage -5 V...+5 V 1 channel used
Voltage -10 V...+10 V 1 channel used
Voltage 0 V...+5 V 1 channel used
Voltage 0 V...+10 V 1 channel used
Standard
Ranges
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/17 3ADR010121, 13, en_US 477