ABB AC500 PLC - Connection of Analog Output Loads (Voltage, Current); Internal Data Exchange; I;O Configuration

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital input 24 V 1 channel used
Effect of incorrect input ter-
minal connection
Wrong or no signal detected,
no damage up to 35 V
Connection of Analog Output Loads (Voltage, Current)
UP
ZP
3.0
O0-
3.1
O1-
3.8
UP
3.9
ZP
PTC
4.0
O0+
4.1
O1+
4.8
UP
4.9
ZP
-10 ... +10 V
0 ... 20 mA
4 ... 20 mA
Fig. 68: Connection example
Voltage -10 V...+10 V Load max. ±10 mA 1 channel used
Current 0 mA...20 mA Load 0 W...500 W 1 channel used
Current 4 mA...20 mA Load 0 W...500 W 1 channel used
Only the channels 0...3 can be configured as current output (0 mA...20 mA or 4 mA...20 mA).
Unused analog outputs can be left open-circuited.
Internal Data Exchange
Digital inputs (bytes) 0
Digital outputs (bytes) 0
Counter input data (words) 4
Counter output data (words) 4
I/O Configuration
The module does not store configuration data itself. It gets its parameterization data from the
master device of the I/O bus (CPU or bus module) during power-up of the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US530