ABB AC500 PLC - 1.7.1.3.9 State LEDs

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
)
This message appears if external voltages at one or more terminals DC0..DC7
or DO0..DO7 cause other digital outputs to be supplied by that voltage (voltage
feedback, see Electrical Connection
Ä
Chapter 1.7.1.3.3 “Electrical Connec-
tion” on page 740). All outputs of the digital output groups will be turned off for
5 seconds. The diagnosis message appears for the whole output group.
5
)
The voltage at digital outputs DC0..DC7 and DO0..DO7 has exceeded the
process supply voltage UP3 (see Electrical Connection
Ä
Chapter 1.7.1.3.3
“Electrical Connection” on page 740). A diagnosis message appears for the
whole module.
6
)
This message appears if the output of a channel DC0..DC7 or DO0..DO7
should be switched on while an external voltage is connected. In this case the
start-up is disabled while the external voltage is connected. Otherwise, this
could produce reverse voltage flowing from this output to other digital outputs.
This diagnosis message appears for each channel.
7
)
Short circuit: After a short circuit has been detected, the output is deactivated
for 100ms. Subsequently, a new start-up will be executed. This diagnosis mes-
sage appears for each channel.
1.7.1.3.9 State LEDs
The LEDs are located at the front of the module. There are 2 different groups:
The 5 system LEDs (PWR, CN-RUN, CN-ERR, S-ERR and I/O bus) show the operation
states of the module and display possible errors.
The 29 process LEDs (UP, UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process
supply voltage and the states of the inputs and outputs and display possible errors.
LED Color OFF ON Flashing
PWR/RUN Green Process supply
voltage missing
Internal supply
voltage OK,
module ready for
communication
with I/O controller
Start-up / pre-
paring communi-
cation
Yellow --- --- ---
CN-RUN Green --- Device config-
ured, CANopen
bus in OPERA-
TIONAL state
and cyclic data
exchange run-
ning
Flashing: CAN-
open bus in PRE-
OPERATIONAL
state and slave is
being configured
Single flash:
CANopen bus in
STOPPED state.
Flickering: Auto-
detect is active
States of the 5
System LEDs
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/173ADR010121, 13, en_US754