Output Ranges Voltage and Current
The represented resolution corresponds to 16 bits.
Range 0...+10 V -10...+10 V 0...20 mA 4...20 mA
Overflow 0 V 0 V 0 mA 0 mA
Measured
value too high
11.5 V 11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0.0007 mA
20.0000 mA
:
4.0006 mA
0.0000 V 0.0000 mA 4.0000 mA
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
Measured
value too low
-1.5 V -10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
Underflow 0 V 0 V 0 mA 0 mA
Range Digital value
Decimal Hex.
Overflow > 32511 > 7EFF
Measured value too high 32511
:
27649
7EFF
:
6C01
Normal range 27648
:
1
6C00
:
0001
0 0000
-1
-6912
-27648
FFFF
E500
9400
Measured value too low -27649
:
-32512
93FF
:
8100
Underflow < -32512 < 8100