1.6.2.1.6 Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configu-
ration.
Module: Module slot address: Y = 1...10
Name Value Internal
Value
Internal
value,
Type
Default Min. Max. EDS Slot
Index
Module ID Intern
1805
1
)
WORD 0x070D 0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
BYTE No
0x00
Not for
FBP
Parameter
length
Internal 42 BYTE 0 0 255
xx02
3
)
Check
supply
Off
On
0
1
BYTE On
0x01
0x0Y03
Input
delay
0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE 8 ms
0x02
0 3 0x0Y04
Mode
Counter 0
see table
below
0 BYTE 0x00 0 15 0x0Y05
Counter 0
frequency
limit
No filter
50 Hz
500 Hz
5 kHz
20 kHz
0
1
2
3
4
BYTE No filter
0x00
0 4 0x0Y06
Counter 0
input level
0-24 V DC
0-5 V DC
Differen-
tial
1 Vpp
sinus
0
1
2
3
BYTE 0-24 V DC
0x00
0 3 0X0Y07
SSI 0 fre-
quency
200 kHz
500 kHz
1 MHz
2
3
4
BYTE 200 kHz
0x02
0 4 0x0Y08
SSI 0 res-
olution (in
bit)
8 to 32 bit BYTE 16 bit
16
8 32 0x0Y09
SSI 0
code type
Binary 0 BYTE Binary
0
0 0 0x0Y0A
2019/04/17 3ADR010121, 13, en_US 663