EasyManua.ls Logo

ABB AC500 PLC - Technical Data of the Analog Outputs; Ordering Data

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Input voltage +15 V Typ. 4.3 mA
Input voltage +30 V < 9 mA
Input resistance ca. 3.5 kW
Technical Data of the Analog Outputs
Parameter Value
Number of channels per module 4, all channels for voltage and current
Distribution of channels into groups 1 group of 4 channels
Channels O0-...O3- Terminals 3.0...3.3
Channels O0+...O3+ Terminals 4.0...4.3
Output type Bipolar with voltage, unipolar with current
Galvanic isolation Against internal supply and other modules
Configurability -10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA (each
output can be configured individually), current out-
puts only channels 0...3
Output resistance (load), as current
output
0 W...500 W
Output loadability, as voltage output Max. ±10 mA
Indication of the output signals One LED per channel
Resolution 12 bits (+ sign)
Conversion error of the analog values
caused by non-linearity, adjustment
error at factory and resolution within
the normal range
Typ. ±0.5 % of full scale
at 25 °C
Max. ±1 % of full scale (all ranges)
at 0 °C...60 °C or EMC disturbance
Relationship between output signal and
hex code
See table
Ä
Chapter 1.5.2.2.4.9.3 “Output Ranges
Voltage and Current” on page 540
Unused outputs Can be left open-circuited
Ordering Data
Part No. Description Product Life Cycle Phase *)
1SAP 250 100 R0001 AX521, analog input/output module,
4 AI, 4 AO, U/I/Pt100, 12 bits + sign,
2-wires
Active
1SAP 450 100 R0001 AX521-XC, analog input/output
module, 4 AI, 4 AO, U/I/Pt100,
12 bits + sign, 2-wires, XC version
Active
*) For planning and commissioning of new installations use modules in Active
status only.