EasyManua.ls Logo

ABB AC500 PLC - Connection of Resistance Thermometers in 2-wire Configuration

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTICE!
Risk of faulty measurements!
The negative pole/earthing potential at the sensors must not have too large a
potential difference with respect to ZP (max. ± 1 V within the full signal range).
Make sure that the potential difference never exceeds ± 1 V.
CAUTION!
The process supply voltage must be included within the earthing concept of the
plant (e. g. earthing of the minus pole).
The module provide several diagnosis functions
Ä
Chapter 1.7.3.1.8 “Diagnosis” on page 848.
The measuring ranges are described in the section Measuring Ranges
Ä
Chapter 1.7.3.1.7
“Parameterization” on page 842
Ä
Chapter 1.7.3.1.10 “Measuring Ranges” on page 851.
The function of the LEDs is described in the section State LEDs
Ä
Chapter 1.7.3.1.8 “Diag-
nosis” on page 848.
Connection of Resistance Thermometers in 2-wire Configuration
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must flow
through them to build the necessary voltage drop for the evaluation. For this, the module CI511-
ETHCAT provides a constant current source which is multiplexed over the max. 4 analog input
channels.
The following figure shows the connection of resistance thermometers in 2-wire configuration.
1.0
1.1
1.8
1.9
AI0+
AI1+
UP
ZP
UP
ZP
PTC
1.5
AI–
1
Fig. 160: Connection of resistance thermometers in 2-wire configuration
1 Pt100 (2-wire), Pt1000 (2-wire), Ni1000 (2-wire); 1 analog sensor requires 1 channel
Device Specifications
Communication Interface Modules (S500) > EtherCAT
2019/04/173ADR010121, 13, en_US832

Table of Contents

Related product manuals