Output Ranges
Range -10 ... +10 V 0 ... 20 mA 4 ... 20 mA Digital value
Decimal Hex.
Overflow > 11.7589 > 23.5178 > 22.8142 32767 7FFF
Output value
too high
11.7589
:
10.0058
:
:
23.5178
:
:
:
20.0058
22.8142
:
:
20.0058
:
32511
:
27664
27658
27656
7EFF
:
6C10
6C0A
6C08
Normal range
Normal range
or output
value too low
10.0000
:
0.0058
:
:
20,0000
:
:
:
0.0058
20.0000
:
:
4.0058
27648
:
16
10
8
6C00
:
0010
000A
0008
0.0000 0 4 0 0000
:
-0.0058
:
:
:
-10.0000
3.9942
:
:
0
-10
-16
-4864
-6912
:
-27648
FFF6
FFF0
ED00
E500
:
9400
Output value
too low
-10.0058
:
-11.7589
-27664
:
-32512
93F0
:
8100
Underflow < -11.7589 <0.0000 -32768 8000
The represented resolution corresponds to 12 bits respectively 11 bits plus sign.
Technical Data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System Data AC500-eCo”
on page 1192
Only additional details are therefore documented below.
Parameter Value
Process supply voltage L+
Connections Terminal 19 for L+ (+24 VDC) and terminal 20 for
M (0 V)
Rated value 24 VDC
Current consumption via L+ terminal 0.14 A + output load
Inrush current (at power-up) 0.05 A
Max. ripple 5 %
Protection against reversed voltage Yes
Device Specifications
I/O Modules > Analog I/O Modules